BE1-11g
2
FEATURES
PROTECTION
• 6 each, Instantaneous Overcurrent (50) elements provide
selection of single or three phase, neutral, zero and
negative seuqence current measurement. Directional and
non-directional operation is a selection Settable definite
time delay is available.
• 7 each, Time Overcurrent (51) elements provide selection
of single or three phase, neutral, zero and negative
sequence current measurement. Voltage control or
restraint characteristics may be selected. The reset
characteristic may be instantaneous or have an inverse
reset characteristic.
• Each Time Overcurrent element may be directional (67/
67N) (forward or reverse) or non-directional. Directional
control may be selected as Positive (I
1
), Negative (I
2
) or
Zero (I
0
) sequence current or zero sequence voltage (V
0
).
• 24 industry standard timing curves are available, as well
as a user programmable curve, and up to 4 user-defined
tabular curves for use by any of the Time Overcurrent
elements.
• Minimal transient overreach and overtravel is incorpo-
rated into the design of the overcurrent elements.
• An independent ground current input provides zero
sequence current polarization and/or ground overcurrent
protection.
• Negative sequence overcurrent is a selectable mode of
operation for the Time Overcurrent elements.
• 5 Phase Undervoltage (27P) and 4 Phase Overvoltage
(59P) elements are available for measurement of phase-
to-phase or phase-to-neutral voltage. Sensed voltage
may be single or three phase. Undervoltage elements
include an undervoltage inhibit setting to prevent errone-
ous operation.
• 4 Undervoltage (27X) and 4 Overvoltage (59X) elements
are available to measure single phase inputs (V
X
) or
calculated sequence voltages (3V
0
, V
2
(47)). These
undervoltage elements include an undervoltage inhibit
setting to prevent erroneous operation.
• All voltage elements have a choice of definite or inverse
time characteristics.
• Overexcitation, volts-per-Hertz (24) element provides a
selection for definite or inverse timing characteristics.
• Sync check (25) with line and bus voltage monitoring
logic (25VM).
• 2 directional power (32) elements measure single or three
phase power, in the forward or reverse direction, and
compare the measurement to an over or under power
user setting.
• A choice of Loss of Excitation functional elements is
provided. An offset VAR flow algorithm (40Q) provides
underexcitation protection. A dual offset mho characteris-
tic (40Z) with voltage suppression provides complete
protection for a loss of excitation.
• Fuse loss detection protects against false tripping due to
the loss of a sensing voltage (60FL).
• 8 frequency elements may be set individually for over,
under, or rate-of-change of frequency. The rate-of-change
can be set for positive, negative, or either. Each element
can be assigned to either the three phase or single phase
(V
X
) voltage input. Each element includes an
undervoltage inhibit setting.
• Breaker Failure (BF) protection functionality.
• 8 general purpose logic timers (62) and additional logic
elements provide added functionality in the user de-
signed BESTLogicPlus schemes.
• 4 protection setting groups with external or automatic
selection modes.
CONTROL
• Five virtual selector switches (43) are controllabe from
both the HMI and communication ports.
• Virtual lockout (86) latches. Status is stored in EEPROM.
• Virtual breaker control switch (101) is controllable from
both the HMI and communication ports.
• Communication port control in the virtual switches
provides SCADA control of the protective system and
circuit breaker.
INSTRUMENTATION
• Real time phase (A, B, C) currents, voltages, and
frequency, as well as the calculated neutral current,
and negative and zero sequence current and voltage.
• Real Time per phase and 3 phase Watts, Vars, and
Power Factor.
• Auxiliary input fundamental and third harmonic voltage.
• Phase angle.
• Demand currents, watts, and vars.
REPORTS
• Current demands for phase, neutral, negative sequence
current, and forward and reverse watts and vars.
Magnitudes and time stamps are recorded for today's
peak, yesterday's peak, and peak since last reset.
• 4000 point log of demand readings.
• kWh and kVarh, forward and reverse.
• Breaker operations counter and contact interruption duty
FAULT RECORDING
• 1028 event sequence-of events report with I/O and
alarm sub-reports.
• Fault Reporting - 1 or 2 oscillographic records per
fault record.
• 16 fault summary reports. All Fault Summary Records
saved in non-volatile memory
• Oscillographic memory will store up to 240 cycles of
data @ 32 samples/cycle
• Oscillographic records are in the COMTRADE format.
• Distance-to-fault is calculated using a load compen-
sated algorithm.
COMMUNICATIONS PORTS
• Three independent general purpose communication
ports and available protocols:
- Front USB-B: BESTCOMSPlus
- Rear RS-485: Modbus™ or DNP
3.0
- Rear Ethernet: BESTNetPlus, BESTCOMSPlus,
Modbus™ and DNP
3.0 protocols
- IRIG-B time sync (unmodulated)
SELF TEST and ALARM FUNCTIONS
• Relay fail, major alarm, and minor alarm LEDs, and
fail-safe alarm output contact (open or closed)
See style chart, page 12, for ordering information.