www.basler.com BE1-87G Percentage-Differential Relay Washington State University Hands-On Relay School
BE1-87G Power-Supply Options Page 1-5 Wide-range, isolated, low-burden, switching Input power (source voltage) is NOT polarity sensitive Type Input Vo
BE1-87G Front-Panel Controls Page 2-1
BE1-87G Stabilizing Reactor Pg 3-2
BE1-87G Operate / Restraint Characteristic Pg 5-4
BE1-87G DC Connections Pg 4-19
BE1-87G AC Connections Pg 4-20
BE1-87G Internal Connections Pg 4-12
BE1-87G NOTE Input reactance might be too great for solid-state test sets at large operate currents Bypass the internal stabilizing reactor by placing
BE1-87G Single-Phase Testing Follow test routine in the instruction manual, at page 5-2 Pg 5-2
BE1-87G External Wiring Pg 1-2
BE1-87G Differential Protection
BE1-87G Three-Phase Internal Connections Pg 4-15
BE1-87G Three-Phase Testing Sense 1–10 I1 (At) 9–8 ∠0° I2 (Bt) 15–14 ∠240° I3 (Ct) 19–18 ∠120° I4 (An) 6–8 ∠180° I5 (Bn) 12–14 ∠60° I6 (Cn) 16–18 ∠30
BE1-87G Testing Differential: Method 1 Set selector switch to D Apply 0.1 amps to terminals 9-6 Ramp up current to terminals 8-6 Relay should pick up
BE1-87G Testing Differential: Method 2 Set selector switch to D Apply 1.0 amps to terminals 9-8 at 1800 Apply 1.0 amps to terminals 6-8 at 00 and ramp
BE1-87G Investigate! Try changing angles (if you can)–does relay respond differently at 300, 900, 1800, etc.? Is there a maximum torque angle? Ramp up
Questions?
BE1-87G 1-∅ Generator Application Stabilizing Reactor
BE1-87G Style Chart Page 1-4
BE1-87G Current-Sensing Inputs • Range 1: 5-A nominal; 10 A contin; 250 A for 1 s • Range 2: 1-A nominal; 2 A contin; 50 A for 1 s • Burden: <
BE1-87G • Minimum Differential (Operate) Current • 0.1, 0.15, 0.2, 0.4, 0.5, 0.8, 1.6 A • Accuracy • For IR ≤ 4 A: ±5% of operate pickup or ±25 mA (w
BE1-87G • Minimum Differential (Operate) Current • 0.02, 0.03, 0.04, 0.08, 0.10, 0.16, 0.32 A • Accuracy • For IR ≤ 0.8 A: ±5% of operate pickup or ±
BE1-87G • Resistive Ratings › 120 Vac: Make, break, and carry 7 Aac continuous › 250 Vdc: Make and carry 30 Adc for 0.2 s, carry 7
BE1-87G Two Types of Targets Page 1-6 Internally operated or current operated targets Internally operated–electronically latching • Manual-reset targe
Comentários a estes Manuais